I get unexpected results when using the program. Why?
The file on common mistakes and recommendations when using Sta4CAD is available here for download.
|
Does STA4-CAD perform a fully three-dimensional analysis?
STA4-CAD performs a fully three-dimensional analysis. It establishes equilibrium equations for six displacements at each point: three degrees of freedom at the points and three in the floor diaphragm. The hexagonal example requires a fully three-dimensional analysis. Modal analysis is likewise performed in three dimensions. Structures with more than five floors must be analyzed in three dimensions. Differences in axial deformation of columns will greatly affect your structural analysis.
|
|
|
 |
Sta4CAD also performs three-dimensional analysis in the mat raft foundation and finite element module. To see the theoretical results for the plate and slab finite elements used in this module and comparisons with other structural programs, click here. |
|
Should multi-leg shear walls in STA4-CAD be defined as polygon columns?
It is preferable to define multi-leg shear walls with an overall contour dimension under 5 m as polygon columns, because all moments of inertia are considered. If one wall leg is longer than 5 m, define panel elements so that deformation behavior can be considered using more nodes.
|
Can a floor be considered a basement if it has a partial basement wall or a wall in only one direction in STA4-CAD?
Modal analysis is an earthquake analysis method that considers all effects on the entire structure, including the foundations. However, the earthquake forces found by modal analysis must be compared with the equivalent earthquake method. Since the equivalent earthquake method calculates seismic forces based on the longest period, the earthquake code separates the seismic loads of the superstructure and basement floors. For a structure with a basement, it requires the seismic calculation to use R=1.5 based on the floor load. This value is much higher than for the superstructure, where R=4~8 is used. If the basement can carry these seismic loads in both directions, you can treat it as a basement.
|
Which axis on a shear wall should I use to define beam axes?
Axes defined for elements in STA4-CAD are purely geometric. Structural analysis is calculated using system axes passing through the centers of gravity of the elements. The structural calculations will not change regardless of where the axes are placed.
|
Why do beam dead loads change in the analysis results after data entry?
Because beams and slabs are defined on the same axis, their dead loads would otherwise be counted twice. The load reduction due to overlapping slabs is therefore applied automatically in the load analysis.
|
 |
|
Can basement walls in STA4-CAD be entered as a single wall along the structure?
Assuming a typical basement wall height of 3 m, it is possible to enter a single wall up to twice this height, or 6 m. However, if a column rests on the middle of the wall, the wall will be subjected to bending under vertical loads, although column loads and eccentricity moments are considered. It will also act like a foundation beam. Therefore, if the wall length exceeds twice its height, a column rests in the middle, or significant beams connect to it, enter it as a panel wall and enable nodal degrees of freedom at every point.
|
Should strengthening walls be entered as panel walls or ordinary rectangular walls?
If you are adding a strengthening wall between two existing columns, the choice depends on the condition of those columns.
If the existing column:
- has concrete quality above BS14,
- has existing longitudinal reinforcement meeting the 0.01 reinforcement ratio,
- has sufficiently closely spaced stirrups,
- and provides an area equal to 10% of the wall area,
it can be modeled as a panel wall. Otherwise, enter it as a rectangular wall independent of the existing columns, thereby recreating the wall boundary zone.
|
When strengthening, is it correct to define E1 as the existing material and E2 as the new element material?
STA4-CAD clearly specifies the definition of existing and new elements. To follow the program's checking logic, enter E1 as new and E2 as existing. Otherwise, automatic jacketing, reports and drawings will not be correct.
Can vertically inclined slabs and beams be entered in STA4-CAD?
Inclined slabs and beams can be entered in STA4-CAD V11. Drawings are also produced according to their elevations. V12 added the ability to use circular slabs and beams.
Can I create a door opening on the lowest floor of a seismic wall?
The lowest part of a wall carrying seismic loads is its most highly stressed region. If an opening not present on the upper floors is made in that wall, the wall might as well not be there. An opening can be created by defining columns and beams in the finite elements.

|
Why do I need very large dimensions to satisfy the confined column check in highly ductile structures?
As in ACI, when beams connect to the narrow side of a column at the edge, the effective shear area for the confined column check is limited to the beam width. This area is insufficient, so very large column dimensions are required under these conditions.
|
Can line loads and point loads be applied to slabs?
In Sta4CAD v13, walls can be defined as line loads on slabs and the defined load is solved using yield lines. If desired, the stairs and slab FEA analysis module can also be used.
|
Which programs can STA4-CAD transfer data to, and can it import data from architectural drawings?
STA4-CAD works with STAAD/PRO, ETABS and SAP2000 for structural data transfer. It can read formwork plans from architectural drawings.
|
Why does STA4-CAD not apply an option after I change it?
Since V9.0, options are customized for each project. Changes to general options therefore affect newly created projects. An existing project will not be affected unless you open it and change its options.
|
What type of wall should be entered for tunnel-form structures?
For tunnel-form structures, panel walls with boundary columns at both ends are preferable. The use of welded wire mesh in panels is an additional advantage.
|
When is a polygon column treated as a shear wall?
A polygon column is treated as a wall if one of its dimensions in either direction exceeds 149 cm. Structural calculations do not change because shear deformation effects are considered for columns and walls of every size. Treating a polygon column as a wall affects reinforced concrete calculations and the wall base moment under the earthquake code.
|
Why does reinforcement in slabs not extend into neighboring slabs?
If slab continuity is defined during STA4-CAD data entry, reinforcement will extend into neighboring slabs.

|
How can I delete an intermediate floor in STA4-CAD?
You can delete a floor using the delete floor command in floor data entry (the same menu also lets you add a floor), or select all elements in the floor editing menu and delete them with the Delete key.
|
 |
|
Why does the program stop when I test an eight-story structure by analyzing it as a one-story structure?
If you have defined eight floors and some floors have no elements, the program may stop. Set the floor count to the number of floors actually created and run the analysis. If an error occurs, check the data and the floor coordinates in the floor information.
|
Why does the program stop while editing reinforcement after analysis?
Some sections may require excessive reinforcement due to heavy structural loading. If the selected reinforcement diameters are also small, the reinforcement will not fit in the section and the program may stop. Open the reinforcement selection section and enable the largest reinforcement diameters.
|
Which versions of Windows does STA4-CAD support?
STA4-CAD can run on Windows XP and Vista. Windows 2000 uses the same kernel as XP and is also compatible, but you should still test the demo on your computer. Operating systems released before these are not supported after V12.
|
Why do I sometimes receive a "no HASP" message while using STA4-CAD?
Check that your dongle is fully connected. If the issue persists, check the parallel port to which it is connected. Do not connect or disconnect any hardware, including the dongle, while the computer is on, as this may damage your computer or hardware.
|
When should finite beams be given the same name?
Giving beams the same or different names does not change the finite-element structural calculations. Using the same name affects only reinforced concrete checks and drawings. If a negative support moment occurs at the shared support of adjacent finite beam segments with the same name, they act as two separate beams. Additional reinforcement must therefore be placed at the top of this junction. This applies to beams K101 and K102, whereas K105 acts as a single beam. The dead-load moment diagram can help determine this, especially for the correct use of bent-up bars.
|
When should I use the FEA module for foundation analysis?
If slab stiffness is too significant to neglect (the slab thickness exceeds one third of the foundation beam thickness), analysis should be performed using the FEA module.

|
Black-and-white output and scale in AutoCAD:
To produce black-and-white output in AutoCAD, follow these steps:
- Open the drawing to be printed.
- Open the drawing's layer properties.

- Select all layers at once.

- Then perform the following steps:
1) Left-click any of the "Normal" entries.
2) Select "monochrome.sdb" in the window that opens.
3) Select the "Style1" style.
4) Press "OK".

- Then press "OK" again to close the layer window. The output color is now set.
Set the scale as follows:
- Go to the print section (Plot from the File menu).
- The print options should be as marked in red below:
1) Drawing area = Limits
2) Scale = mm
3) Ratio: 1000 mm = 1 unit

|
How is the length of column starter bars calculated?
Consider the following points when calculating column starter bar lengths:
|
 |
(TS500 formula 9.1) |
| |
|
|
|
For plain bars, the lb development length must be multiplied by 2. |
(TS500) |
| |
|
|
|
In the general case (Position I), the lb development length must be multiplied by 1.4. |
(TS500) |
|
 |
(TS500) |
| |
|
|
|
If more than 50% of the longitudinal reinforcement is spliced at the bottom of the column, the lap splice length must be at least 1.5 times lb. This condition also applies to column starter bars projecting from the foundation. |
(Earthquake Code) |
| |
|
|
|
lb development length should not be less than 40f. |
|
These rules can be illustrated as follows:
Example 1: f16, C20, S420, for a column element:
fctd » 10.4
lb = 0.12 ´ (3652 / 10.4) ´ 1.6 » 67 cm (also multiplied by 1.4 for beams)
40 ´ f = 64cm < 67cm, lb = 67 cm is calculated.
In addition, the development length under the earthquake code is: 1.5 ´ 67 cm = 101 cm.
Example 2: f14, C20, S220, for a beam element:
lb = 0.12 ´ (1913 / 10.4) ´ 1.4´ 1.4 ´ 2 » 87 cm.
|